MAMM-WSHP-IOM-1UB (September 2011) Single Circuit Horizontal and Vertical Water Source Heat Pumps With R-410A Installation, Operation and Maintenance
10 MAMM-WSHP-IOM-1UB (September 2011) 1. Open all valves to full open position and turn on power to the heat pump. 2. Set room temperature sensor f
11 MAMM-WSHP-IOM-1UB (September 2011) Operating Limits Application Limits WATER TEMPERATURES / Degrees F * Standard range Low Temp Geothermal C
12 MAMM-WSHP-IOM-1UB (September 2011) MAMMOTH CONTROLS I/O 560 Mammoth I/O Zone 560 controller delivers powerful control and communications fe
13 MAMM-WSHP-IOM-1UB (September 2011) I/O 560 (Base CAV) - Examples of I/O’s Universal Input Jumper Setting 1 Supply Air Temperature (Monitor
14 MAMM-WSHP-IOM-1UB (September 2011) I/O 583 Mammoth I/O Zone 583 controller delivers powerful control and communications features all in a c
15 MAMM-WSHP-IOM-1UB (September 2011) I/O Zone 583 (RHT, CAV, NMUA) - Examples of I/O’s Options are in italics. Common options are bolded. * Cost
16 MAMM-WSHP-IOM-1UB (September 2011) I/O Flex 6126 The standard factory-integrated DDC controller provides control flexibility that can be easi
17 MAMM-WSHP-IOM-1UB (September 2011) Examples of I/O’s INPUTS Point Description UD #1 +Pulse BMS Supply Air, Duct Static Reset or Room Air Tempera
18 MAMM-WSHP-IOM-1UB (September 2011) MAMMOTH DDC CONTROLS Keypad Locally access controllers and operational properties with the easy-to-use BACview6
19 MAMM-WSHP-IOM-1UB (September 2011) Normal maintenance on U-Vintage horizontal and verti-cal units is generally limited to filter changes. Air fil
2 MAMM-WSHP-IOM-1UB (September 2011) Model Nomenclature ·····························································································
20 MAMM-WSHP-IOM-1UB (September 2011) Troubleshooting R-410A The In’s and Out’s of R-410A R-410A is a non-ozone depleting blend of two Refrigerants —
21 MAMM-WSHP-IOM-1UB (September 2011) Performance Troubleshooting Performance Troubleshooting Heating Cooling Possible Cause Solution Insufficient
22 MAMM-WSHP-IOM-1UB (September 2011) UNIT CHECK-OUT SHEET Customer Data Customer Name ________________________________________ Date ____________
Mammoth, Inc. has a policy of continuous product improvement and reserves the right to change design and specifications without notice. © 2011 Mammo
3 MAMM-WSHP-IOM-1UB (September 2011) “Mammoth” is a registered trademark of Mammoth, Inc. ©Mammoth, Inc. 2011. All rights reserved through
4 MAMM-WSHP-IOM-1UB (September 2011) Installation General 1. To prevent damage, this equipment should not be operated for supplementary heating a
5 MAMM-WSHP-IOM-1UB (September 2011) Unit Location and Clearances The diagrams below show minimum suggested clear-ances. Any additional clearance
6 MAMM-WSHP-IOM-1UB (September 2011) Mounting Vertical units can be mounted on the floor or a concrete pad, typically in a mechanical closet or ot
7 MAMM-WSHP-IOM-1UB (September 2011) Ductwork and Attenuation Discharge ductwork is normally used with U-vintage horizontal and vertical single circu
8 MAMM-WSHP-IOM-1UB (September 2011) Supply Piping 1. All heat pumps should be connected to supply and return piping in a two-pipe reverse return co
9 MAMM-WSHP-IOM-1UB (September 2011) 1. Prior to first operation of U-Vintage horizontal and vertical units, the water circulation system must be cl